Inspection History Details
Inspection Status: Partial Approval
Inspection History: PLUMBING - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/12/2006 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* WATER TEST WASTE & VENT KITCHEN AREA OK 1. PROVIDE CORRECT COUPLINGS & REPAIR LEAKS AT JANITOR SINK VENT IN WALL AND RETEST. WATER TEST WASTE & VENT THRU ROOF ALL OTHER AREAS OK WATER PIPING OK CLOSET FLANGES OK |
|
| 07/12/2006 | PLUMBING - INTERMEDIATE | Approved | IVRS - Inspection :* WASTE & VENT THRU ROOF OK CLOSET FLANGES OK WATER PIPING OK |
|
| 07/10/2006 | PLUMBING - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* PROVIDE TESTING ON ALL PIPING SPOKE WITH PLUMBERS & GENERAL ON STIE ABOUT REQUIREMENTS. |
|
| 06/28/2006 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* 1) THESE INSPECTIONS SHALL REQUIRE EXOPOSURE OF PIPING, TESTING 2) REVISED APPROVED FROM CITY PLANS SHALL BE REQUIRED FOR RELOCATED GAS AND FIXTURES 3) BAR AREA SHALL BE COMPLETE FOR TEMPORARY USE, ALL BACK FLOW CERTIFICATIONS WILL BE NECESSARY 4) SEE PAST NOTES FOR COMPLETION OF GAS SYSTEM 5) NO GAS CARD WILL BE ISSURED UNTIL GAS PIPING IS EXPOSED, TESTED AND A COMPLETE GAS SYSTEM 6) ALL HOSE BIBS TO HAVE VACUUM BREAKERS, ALL OPEN SANITARY DRAINS SHALL BE CAPPED TO PREVENT UN-SANITARY CONDITION 7) THIS IS NOT A COMPLETE LIST |