Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
08/05/2006 ELECTRIC - FINAL Approved IVRS - Inspection :*
1. LOW VOLTAGE LIGHTING POWER BOXES --
SUPPORT & GROUND USE APPROVED FITTINGS - MISSING BOX.
08/02/2006 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
FIXTURES STILL ON BACK ORDER
07/28/2006 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1. WAITING ON FRONT LIGHT
2. FINISH OUTSIDE AS DISCUSSED
06/30/2006 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
RECEIVED CHECK #31314 FOR AFTER HRS INSPECTION 108.00
INTERIOR ITEMS CORRECTED -- FINISH EXTERIOR AS DISCUSSED INTERIOR OK SUBJECT TO OTHER INSPECTORS APPROVAL AND DETERMINATION OF STEVE LONG.
06/29/2006 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1. FINISH PREVIOUS ITEMS
2. EMERGENCY LIGHTING TO BE AS PER 700.12
3. FINISH ELECTRIC
06/27/2006 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1) NEED SUPPORT WIRES ON CANS, EXIT LIGHTING AND FIXTURES
2) A DISCONNECTING MEANS FOR ICE MACHINE IS NEEDED
3) FINISH ELECTRIC AS DISCUSSED
4) OK 2 POLE BASES
5) OK PVC ACROSS DRIVEWAY AND PARKING LOT
05/01/2006 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1. PREVENT OBJECTIONABLE CURRENT 250.6
2. BOND METER SERVICE NIPPLE
3. PLANS CALL FOR 42 KAIG "MDP" WE HAVE 22 KAIG
4. PLANS CALL FOR XHHW-2 WE HAVE THHN-THWN-2