Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/05/2006 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* 1. LOW VOLTAGE LIGHTING POWER BOXES -- SUPPORT & GROUND USE APPROVED FITTINGS - MISSING BOX. |
|
| 08/02/2006 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* FIXTURES STILL ON BACK ORDER |
|
| 07/28/2006 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. WAITING ON FRONT LIGHT 2. FINISH OUTSIDE AS DISCUSSED |
|
| 06/30/2006 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* RECEIVED CHECK #31314 FOR AFTER HRS INSPECTION 108.00 INTERIOR ITEMS CORRECTED -- FINISH EXTERIOR AS DISCUSSED INTERIOR OK SUBJECT TO OTHER INSPECTORS APPROVAL AND DETERMINATION OF STEVE LONG. |
|
| 06/29/2006 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. FINISH PREVIOUS ITEMS 2. EMERGENCY LIGHTING TO BE AS PER 700.12 3. FINISH ELECTRIC |
|
| 06/27/2006 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) NEED SUPPORT WIRES ON CANS, EXIT LIGHTING AND FIXTURES 2) A DISCONNECTING MEANS FOR ICE MACHINE IS NEEDED 3) FINISH ELECTRIC AS DISCUSSED 4) OK 2 POLE BASES 5) OK PVC ACROSS DRIVEWAY AND PARKING LOT |
|
| 05/01/2006 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. PREVENT OBJECTIONABLE CURRENT 250.6 2. BOND METER SERVICE NIPPLE 3. PLANS CALL FOR 42 KAIG "MDP" WE HAVE 22 KAIG 4. PLANS CALL FOR XHHW-2 WE HAVE THHN-THWN-2 |