Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/14/2006 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection :* FINISH EXTERIOR |
|
| 04/27/2006 | ELECTRIC - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* | |
| 04/13/2006 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* OK 102, 103, 107, 109, 110, 112 1. NM CABLE NOT ALLOWED IN PLACES OF ASSEMBLY 518.2(A) & 518.4(A) 2. VDV CABLING TO BE PROTECTED FROM SHARP EDGES AT STUDS AND SUPPORTED. 3. PROTECT M/C CABLE IN STOP CHANNEL. 4. FINISH SUPPORTING BOXES. 5. FINISH VDV CABLING. 6. NO MORE THAN 360 DEGREE IN A CONDUIT RUN. |