Permit: T05CM05562

Parcel: 12112044B


Addresses:

5225 E SPEEDWAY BL

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
07/14/2006 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
05/16/2006 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) OK WATER FOUNTAINS EAST & WEST WALL AND RECEPTACLE LIGHTING SWITCHES (4)
2) OK ROOM #124
3) NOTE: A.I.C. RATING OF PANEL BOARD MDP IS 200,000 RMS
4) 600 AMP MAIN BREAKER RATING IS 56,000 A.I.C.
5) 150 AMP BREAKERS ARE 42,000 A.I.C.
6) 100, 70, 60, 50 & 30 AMP BREAKERS ARE RATED AT 65,000 A.I.C.
7) NOTE: THE AVAILABLE FAULT CURRENT IS LISTED AT 27,000 PER MCGETRIC ENGINEERING. THIS EQUIPMENT IS ADEQUATELY BRACED
8) OK REMOVED DBL BONDING OF NEUTRAL BONDED AT C.T. CABINET (OK PER R. MAJUTA)
9) BONDING LOCK NUT INSTALLED
05/01/2006 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
04/27/2006 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
04/13/2006 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
03/29/2006 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
ELEC. SERVICE U.G.
03/28/2006 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
03/21/2006 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK HARD CEILINGS & ROUGH WALLS AS CLOUDED ON LIGHTING PLAN.
NOTE OK U.G. TO SING OK U.G. @ PARKING LOT (LIGHTING)