Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/14/2006 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 05/16/2006 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) OK WATER FOUNTAINS EAST & WEST WALL AND RECEPTACLE LIGHTING SWITCHES (4) 2) OK ROOM #124 3) NOTE: A.I.C. RATING OF PANEL BOARD MDP IS 200,000 RMS 4) 600 AMP MAIN BREAKER RATING IS 56,000 A.I.C. 5) 150 AMP BREAKERS ARE 42,000 A.I.C. 6) 100, 70, 60, 50 & 30 AMP BREAKERS ARE RATED AT 65,000 A.I.C. 7) NOTE: THE AVAILABLE FAULT CURRENT IS LISTED AT 27,000 PER MCGETRIC ENGINEERING. THIS EQUIPMENT IS ADEQUATELY BRACED 8) OK REMOVED DBL BONDING OF NEUTRAL BONDED AT C.T. CABINET (OK PER R. MAJUTA) 9) BONDING LOCK NUT INSTALLED |
|
| 05/01/2006 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* | |
| 04/27/2006 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* | |
| 04/13/2006 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
| 03/29/2006 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* ELEC. SERVICE U.G. |
|
| 03/28/2006 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
| 03/21/2006 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK HARD CEILINGS & ROUGH WALLS AS CLOUDED ON LIGHTING PLAN. NOTE OK U.G. TO SING OK U.G. @ PARKING LOT (LIGHTING) |