Permit: T05CM05561

Parcel: 108240860


Addresses:

2490 E RIVER RD

Inspection Status: Approved

Inspection History: MECHANICAL - ABOVE CEILING

Date Description Inspector Results Comments
07/05/2006 MECHANICAL - ABOVE CEILING Approved IVRS - Inspection :*
OK TO COVER BALANCE OF GRID 1ST FLR.
06/07/2006 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
OK RMS. AREA B OVER HARD LIDS.
05/24/2006 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
1. AREA A = RETURN PLENIUM. OK TO COVER HARD LIDS IN "A"
2. AREA B = PROGRESSING. SOILED HOLDING,
RM. #141 - OK TO COVER
RM. #140 - OK TO COVER
05/18/2006 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
1. WIRE IN PLENIUM, PLENIUM RATED, OK
2. NEED COPIES OF INSUL. FROM CONTRACTOR VERIFYING PLENIUM RATED GLASS INSUL.
05/12/2006 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
05/09/2006 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
1. 1ST FLR. AREA A, AIR HANDLER AHU? PLENIUM, INSULATION CONTRACTOR WILL VERIFY IN WRITING THAT INSULATION BOLTS ARE PLENIUM RATED.
2. 2ND FLR. HARD LIDS, SUPPLY/RETURN SYSTEMS, OK
OK TO COVER
04/27/2006 MECHANICAL - ABOVE CEILING Partial Approval MEDIUM PRESSURE DUCT OK FOR INSULATION 1ST FLOOR AREA A & MEDIUM & LOW PRESSURE DUCT AREA B - 1ST FLOOR
04/10/2006 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
1. 2ND FLR. OK TO START WRAPPING
2. 1ST FLR. WRAPPED OPENINGS, MED. GAS
STORAGE ROOM - OK