Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/10/2006 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 07/12/2006 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. USE PROPER CLAMPS FOR PIPE BONDING TERMINATIONS. |
|
| 07/11/2006 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) SIZE RACEWAY BONDING JUMPERS PROPERLY NEC 250.102 (C) 2) SIZE BONDS TO WATER, GAS AND BLDG STEEL PROPERLY-NEC 250.104 AND ALL METAL PIPE SYSTEMS |
|
| 05/02/2006 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK TO COVER ELECTRICAL IN WALLS ON MAIN LEVEL. |
|
| 04/11/2006 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK TO COVER ELECTRICAL IN WALLS ON 2ND LEVEL AND 2ND LEVEL PATIO. |
|
| 03/24/2006 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* | |
| 03/14/2006 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK TO COVER UNDERGROUND IN PANEL/ROOM SERVICE |