Inspection Status: Approved
Inspection History: FRAMING
Permit Number - T05CM05552
Inspection Description - FRAMING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/24/2006 | FRAMING | Approved | IVRS - Inspection :* 1) ITEM 03050 NOT REQUIRED/ALL ELECTRIC 2) CAULK ALL PENETRATIONS AT STUCCO LATH |
|
05/22/2006 | FRAMING | Partial Approval | IVRS - Inspection :* 1) CAULK ALL PENETRATIONS STUCCO 2) BLOCK ALL MECH DUCTS 3) BACKING AT FRONT TUB WALL 4) NEW DWV TEST, TWO SCREW HOLES IN 3" ABS 5) CAPPED PIPE, ONE NAIL IN MASTER TOILET ROOM 6) RE-INFORCE TUB FRAME, MASTER 7) FIRE BLOCK DBL FHA STRAP KITCHEN RANGE |