Permit: T05CM05548

Parcel: 140420200

Inspection Status: Approved

Inspection History: PLUMBING - INTERMEDIATE

Date Description Inspector Results Comments
01/25/2006 PLUMBING - INTERMEDIATE Approved IVRS - Inspection :*
01/19/2006 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
12/07/2005 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
PIPING INSULATED WITH 1/2 ARMOR FLEX
PLAN SPECS. 1" FIBERGLASS INSULATION.
PROVIDE A STAMPED LETTER FROM ARCHITECT ALLOWING ARMORE FLEX OR INSTALL PER PLAN.
12/06/2005 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*WATER PIPING TYPE L COPPER 50 PSI OK
WASTE & VENT WATER TEST OK
CALL FOR INSULATION INSPECTION
PIPE WRAPS
CLOSET FLANGES NOT INSTALLED
CALL FOR CLOSET FLANGE INSPECTION
12/05/2005 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
12/01/2005 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :* CORRECTIONS FROM PREVIOUS INSPECTION NOT MADE.
2 % SLOPE REQUIRED
1 1/0 ALLOWED WITH PRIOR APPROVAL FR SPECIAL CONDITIONS.
5 PSI TEST REQUIRED
11/30/2005 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*