Permit: T05CM05539

Parcel: 141015640

Inspection Status: Approved

Inspection History: FRAMING

Permit Number - T05CM05539

Inspection Description - FRAMING

Inspection Status - Approved

Date Description Inspector Results Comments
04/12/2006 FRAMING Approved IVRS - Inspection :*
03/17/2006 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) WRONG ADDRESS ON SERVICE PANEL
2) METAL FIRE BLOCK AT CEILING PENETRATION
3) NEED INSTALLATION REQUIRED FOR H20 HTR
4) NEED TO KNOW WHAT AMPERAGE WILL BE REQUIRED FOR FURNACE, SIZE PER LABEL ON UNIT NOT PER PLAN
5) GAS TEST GAUGE BROKEN
6) KEEP PEX H20 PIPE 12" FROM CAN LIGHTS
7) STRAP B/PLATE REAR LAVS
8) NEED SECONDARY CONDENSATE FROM OVERFLOW PAN
9) TOP PLATE CUT AT OVEN DUCT
10) TRAP TO SAME AS TRAP ARM 42" MAX 1 1/2" AT SOUTH LAV
11) ROMEX OUT OF WALL AT SOUTH TUB, MECH DUCT SAME BATH