Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/26/2006 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* 1) OK RECEIVED LETTER FROM R. SMYTH P.E. HAS REINSPECTION SITE-OK CORRECTIONS MADE |
|
| 06/22/2006 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* NOTE: 1. DISCONNECT FOR HUMIDIFIER IN VIOLATION OF DEDICATED WORKING SPACE #2 2. ENGINEER TO FOLLOW UP ON CORRECTIONS OF EQUIP. INSP. IN CLEAN ROOM. |
|
| 05/15/2006 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. INSTALL PANEL SCHEDULES & LABELS. 2. PROVIDE LISTINGS FOR EQUIP. IN CLEAN ROOM NEC 110-3 |