Permit: T05CM05535

Parcel: 125130890


Addresses:

3221 E 3RD ST

Inspection Status: Approved

Inspection History: PLUMBING - INTERMEDIATE

Date Description Inspector Results Comments
09/25/2007 PLUMBING - INTERMEDIATE Approved IVRS - Inspection :*
SHOWER PAN OK
05/30/2007 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
05/30/2007 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
CORRECTIONS MADE OK
OK TO COVER ALL AREAS
TUBS OK
FLANGES OK
WILL NEED TO SEE SHOWER LINER ON 2ND FLOOR
05/21/2007 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
1. FIRST FLOOR CLOSET FLANGES TO BE SCREWED TO THE FLOOR.
2. SEE NOTE #1 FROM 5/15/07
3. NO MATERIAL SPEC'S SHOWN ON PLAN
PROVIDE BLDG SPEC'S
4. HORIZONAL X HORIZONTAL CHANGE OF DIRECTION TO BE A SWEEP.
05/17/2007 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
COMPLETE LIST FROM 5/15/07
05/15/2007 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. ABS SHALL BE SUPPORTED AT EACH CHANGE OF DIRECTION OR ELEVATION AND AT THE END OF BRANCHES, THEN NO MORE THAN FOUR FEET BETWEEN HANGERS.
2. CLOSET FLANGES SHALL BE SECURED TO THE FLOOR BY APPROVED METHODS.