Inspection History Details
Permit: T05CM05532
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/25/2006 | ELECTRIC - FINAL | Approved | NEED UL STICKER AND LETTER | |
| 08/23/2006 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* | |
| 08/22/2006 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
| 08/16/2006 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. PLEASE VERIFY PATH TO GROUND FOR BUILDING STEEL. 2. PROVIDE AS BUILT FOR LIGHTING SYSTEM 3. FINISH PREVIOUS ITEMS. OK FOR TEMP C OF O FOR TRAINING OF HELP NO PATIENT CARE |
|
| 08/14/2006 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. SUPPORT VDV CABELING 2. FINISH WATER HEATER ROOM 3. VERIFY LISTING FOR CREMTRON MED. GAS UNIT & MED VAC PUMP 4. USE APPROVED FITTING WITH LB. CHASE NIPPLE NOT APPROVED 5. BOXES MORE THAN 1/4" FROM BOX TO SURFACE NEED APPROVED EXTENDER RING. ALSO FLUSH AT COMBUSTIBLES. 6. FINISH UNDER CABINET LIGHTING 7. CT DISCONNECT DOUBLE LUG & 250.97 8. FINISH RECEPTION COUNTER |