Permit: T05CM05532

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
08/25/2006 ELECTRIC - FINAL Approved NEED UL STICKER AND LETTER
08/23/2006 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
08/22/2006 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
08/16/2006 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1. PLEASE VERIFY PATH TO GROUND FOR BUILDING STEEL.
2. PROVIDE AS BUILT FOR LIGHTING SYSTEM
3. FINISH PREVIOUS ITEMS.
OK FOR TEMP C OF O FOR TRAINING OF HELP
NO PATIENT CARE
08/14/2006 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1. SUPPORT VDV CABELING
2. FINISH WATER HEATER ROOM
3. VERIFY LISTING FOR CREMTRON MED. GAS UNIT & MED VAC PUMP
4. USE APPROVED FITTING WITH LB. CHASE NIPPLE NOT APPROVED
5. BOXES MORE THAN 1/4" FROM BOX TO SURFACE NEED APPROVED EXTENDER RING. ALSO FLUSH AT COMBUSTIBLES.
6. FINISH UNDER CABINET LIGHTING
7. CT DISCONNECT DOUBLE LUG & 250.97
8. FINISH RECEPTION COUNTER