Permit: T05CM05521

Parcel: 117060220


Addresses:

617 E 9TH ST

Inspection Status: Approved

Inspection History: PLUMBING - INTERMEDIATE

Date Description Inspector Results Comments
01/26/2006 PLUMBING - INTERMEDIATE Approved IVRS - Inspection :*
1) CORRECTIONS MADE OK
2) OK TO COVER ALL AREAS S.T.O.I.
01/24/2006 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. YARDWATER COVERED W/O INSPECTION
2. SEWER IS P.O.C TO BLDG. DRAIN
3. N/H GROUND IS NOT APPROVED CONNECTOR BETWEEN GALVANIZED AND ABS
4. DIELECTRIC UNIONS MAY NOT BE IN AN INACCESSIBLE LOCATION
5. SUPPORT OVERHEAD PIPING - SUPPORT VERTICAL PIPING
6. SUPPORT UNDER FLOOR PIPING
ABS - EVERY FOUR FEET
EACH CHANGE OF DIRECTION OR ELEVATION AND END OF BRANCHES.
7. CSST NOT APPROVED MATERIAL ON PLAN