Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T05CM05521
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/10/2006 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
04/07/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : There is no access to the site.| 920* LOCKED |
|
04/06/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : There is no access to the site.| 920* |
|
03/30/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 619 E 9TH ST -- 1. BEDROOM CIRCUIT ARC FAULT IS NOT WORKING. 2. BOND GAS & WATER 3. REVISE PLANS REGARDING SUB PANEL 4. SEAL UNUSED OPENINGS AT FURNACE J-BOX 5. INSTALL CORRECT FUSING 6. INSTALL RECEPT. AT FRONT OF HOUSE. 7. ARC FAULT DIDN'T TRIP AT N. WEST BEDROOM LOCATE WATER BONDING LOCATION FOR OUR NEXT INSP. |