Permit: T05CM05506

Parcel: 13110034A


Addresses:

5504 E 22ND ST #100


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T05CM05506

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
05/19/2006 ELECTRIC - FINAL Approved IVRS - Inspection :*
05/16/2006 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1. SEAL 3/4" OPENING AT TOP OF PANEL WHERE #4 COPPER ENTERS PANEL.
2. INSTALL PANEL SCHEDULE.
3. PROVIDE LIGHTING PLAN.
05/15/2006 ELECTRIC - FINAL Partial Approval 5:00 AM (5-15-06) SCHEDULED AFTER HOURS INSPECTION
FIELD COLLECTED $108.00 CHECK #11442 JP TUCKER CONST. INC.
OK SERVICE WORK
TEP ENERGIZED EQUIPMENT (NO CLEARANCE REQ'D)
05/04/2006 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
05/03/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
The service is not per code.| 210*
SERVICE INSPECTION ONLY
1. NEED BUSHINGS FOR #4 AND LARGER CONDUCTORS
NEC 300
2. IDENTIFY GROUNDED CONDUCTOR NEC 200.
3. BOND SERVIE RACEWAY NEC 250
4. GROUNDED CONDUCTOR AND BONDING CONDUCTOR RUN PARALLEL AND WILL HAVE OBJECTIONABLE CURRENT ON BONDING CONDUCTOR NEC 250.6
5. NEED MINIMUM #4 CU BONDING CONDUCGTOR FOR SERVICE NEC 250.66
6. MAKE UP A PHASE SO YOU DON'T HAVE EXCESS CONDUCTOR IN METER NEC 110.
7. INSTALL ADDRESS ON SERVICE, INSTALL L.B COVER.
8. IDENTIFY SERVICE DISCONNECT NEC 230