Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
Permit Number - T05CM05502
Inspection Description - FRAMING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/10/2006 | FRAMING | Approved | IVRS - Inspection :* | |
05/08/2006 | FRAMING | Denied | IVRS - Inspection : There is no plan or job inspection card on site.| 925* 1) NO PLANS/PERMIT ON SITE |
|
05/02/2006 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) ITEMS FROM 4/13/06 NOT DONE 2) ANCHOR BOLTS LOOSE 3) REVERSE PITCH LAV DIRTY ARM 4) SHEARWALL #5 HOLDOWN IN WRONG LOCATION SEE PLAN 5) 17/D-1 NOT NAILED AT 12" ON CENTER |
|
04/13/2006 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) FROM LAST INSPECTION TRUSSES FRONT BEDROOM 3 PST BEARING TWO TRUSSES ARE IN WRONG LAYOUT, ROOF IS LOADED 2) LEAVE TRUSS DRAWINGS OR INSTALL LATERAL BRACES AT GARAGE ABOVE DEAD WOOD 3) BLOCK OUT AT DUCTS IN GARAGE LID 4) LOCATE ATTIC ACCESS 5) NOTE EXT. CABLE WIRES IN REAR POP-OUT |