Permit: T05CM05464

Parcel: 118272670

Inspection Status: Approved

Inspection History: FRAMING

Permit Number - T05CM05464

Inspection Description - FRAMING

Inspection Status - Approved

Date Description Inspector Results Comments
02/24/2006 FRAMING Approved IVRS - Inspection :*
02/22/2006 FRAMING Partial Approval IVRS - Inspection :*
1) PENDING MECH
2) ITEMS 2 AND 5 FROM PREVIOUS
02/17/2006 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) WIRE EXHAUST FAN 2ND FLOOR BATH AND LAUNDRY
2) COMPLETE CONDENSATE COPPER
3) STAPLE WIRES 8" FROM BOX
4) COMPLETE WIRING 2ND FLOOR BATH
5) COMPLETE CONDENSATE DRAIN
6) FIRESTOP MECH CHASE TOP OF STAIRS
7) APPROVED TO INSULATE
02/16/2006 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) COMPLETE LATH
2) STAPLE LATH 6" ON CENTER TOP OF GARAGE WALL
3) SEAL ALL PENETRATIONS THRU LATH OVER MASTER BEDROOM WINDOW
4) BLOCK HVAC BOOT IN LAUNDRY
5) SECONDARY LANDING FOR UPPER RUN OF STAIRS DOESN'T SPAN WALL TO WALL
6) SECOND FLOOR STRAPS NOT NAILED TO STUDS-MASTER BED
7) FIRE BLOCKS MASTER CLOSET
8) FIRE STOP 2ND FLOOR PENETRATIONS
9) PLUMBING, KITCHEN HOOD VENT AND DRYER VENT DIRECTLY OUTSIDE 2ND FLOOR WINDOW
10) STOPPED INSPECTION