Permit: T05CM05449

Parcel: 124041020

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T05CM05449

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
05/26/2006 ELECTRIC - FINAL Approved IVRS - Inspection :*
05/24/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. HAVE OVERFILLED J-BOX AT CASH WRAP.
2. HAVE DEAD RECEPT. N.E CORNER
3. EMERGENCY LIGHTING IS NOT PER PLAN AND SOME EMERGENCY LIGHTING IS BLOCKED BY DISPLAYS.
4. PANEL DIRECTORY IS NOT MARKED CORRECTLY.
5. PROVIDE EARTH GROUND TO ALARM PANEL.
6. RTU DOES NOT APPEAR TO BE WORKING PROPERLY AND HAS BROKEN STAT RACEWAY.
05/19/2006 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
HAVE POWER ON FOR INSPECTION.