Permit: T05CM05448

Parcel: 111071610

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T05CM05448

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
01/06/2006 ELECTRIC - FINAL Approved IVRS - Inspection :*
01/04/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1) CORRECTIONS NOT MADE
12/29/2005 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1. TIGHTEN CONNECTOR TO CABLE AT HOOD
2. BOXES MORE THAN 1/4" FROM BOX TO SURFACE TO USE AN APPROVED EXTENDER RING 314.20
3. LABEL BREAKERS
4. PLEASE IDENTIFY GROUNDED CONDUCTOR
5. FINISH ITEMS 1 & 3 OF PREVIOUS INSPECTION
12/28/2005 ELECTRIC - FINAL Denied IVRS - Inspection :
The inspector was unable to locate the job.| 945*
1) CANNOT LOCATE-CANNOT REMEMBER WHICH UNIT BUILDING NOT ADDRESSED