Permit: T05CM05439

Parcel: 11005531A

Inspection Status: Approved

Inspection History: PLUMBING - INTERMEDIATE

Permit Number - T05CM05439

Inspection Description - PLUMBING - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
01/04/2007 PLUMBING - INTERMEDIATE Approved IVRS - Inspection :*
09/19/2006 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK TO INSULATE
09/14/2006 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
- SEE PREVIOUS INSPECTION
- SAFETY PLATES SHALL BE FHA STRAPS
- SWEEPS REQUIRED
- CLOSET FLANGES SHALL BE SECURELY FASTENED
- WATER PIPNG MAINS AND STUB OUTS IN WEST,
HAVE W/100 PSI TEST.
- OK TO INSULATE PER SPECS.
- ROOF DRAINS OK
- CALL FOR INSPECTIONS NOT YET APPROVED 3005, 3015
08/15/2006 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
1. UNABLE TO LOCATE PLAN OR PERMIT
2. HORIZ X HORIZ CHANGE OF DIRECTION ON DRAINAGE PIPING TO BE A SWEEP.
3. SUPPORT VERTICAL PIPE AS REQ'D BY CODE
SUPPORT OVERHEAD PIPE PER TABLE 3-1 2003 UPC
4. NO INSULATION ON HOT WATER PIPING.
08/11/2006 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
DWV NOT ON TEST
RDS NOT COMPLETE
SAFETY PLATES MISSING
MEDICAL VALVE BOXES INSTALLED
SCHEDULE A MED GAS PRE-CON MEETING