Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
Permit Number - T05CM05439
Inspection Description - PLUMBING - INTERMEDIATE
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/04/2007 | PLUMBING - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 09/19/2006 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK TO INSULATE |
|
| 09/14/2006 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* - SEE PREVIOUS INSPECTION - SAFETY PLATES SHALL BE FHA STRAPS - SWEEPS REQUIRED - CLOSET FLANGES SHALL BE SECURELY FASTENED - WATER PIPNG MAINS AND STUB OUTS IN WEST, HAVE W/100 PSI TEST. - OK TO INSULATE PER SPECS. - ROOF DRAINS OK - CALL FOR INSPECTIONS NOT YET APPROVED 3005, 3015 |
|
| 08/15/2006 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* 1. UNABLE TO LOCATE PLAN OR PERMIT 2. HORIZ X HORIZ CHANGE OF DIRECTION ON DRAINAGE PIPING TO BE A SWEEP. 3. SUPPORT VERTICAL PIPE AS REQ'D BY CODE SUPPORT OVERHEAD PIPE PER TABLE 3-1 2003 UPC 4. NO INSULATION ON HOT WATER PIPING. |
|
| 08/11/2006 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* DWV NOT ON TEST RDS NOT COMPLETE SAFETY PLATES MISSING MEDICAL VALVE BOXES INSTALLED SCHEDULE A MED GAS PRE-CON MEETING |