Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/14/2006 | FRAMING | Approved | IVRS - Inspection :* | |
| 03/10/2006 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) OUTSIDE HOSE BIBS MUST HALF ANTI-SIPHON VALVES 2) WATER HEATER B-VENT OFF SET CANNOT EXCEED 60 DEGREE FROM VERTICAL 3) PLUMBING LEAKS AT LAUNDRY 4) PLUMBING OUT OF WALL CAVITY IN LIVING ROOM 5) WIRE TRAPPED BY DWV 6) HORIZONTAL DWV MUST HAVE 1/4" PER FOOT PITCH 7) NORTH HOLDOWN NUT MUST FULL THREAD BOLT 8) FIRE STOP CHASE BR 2 9) MASTER BATH LAV TRRAP WEIR CANNOT BE HIGHER THAN VENT OPENING ALSO EXCESSIVE PITCH 10) ONLY ONE B-VENT OFF SET OF GREATER THAN 45 PERCENT ALLOWED ON WATER HEATER VENT 11) NAIL PROTECT PLUMBING |
|
| 03/06/2006 | FRAMING | Denied | IVRS - Inspection : Work is not complete enough to inspect.| 950* 1) WATER HEATER B-VENT OFF SET CANNOT EXCEED 60 DEGREE FROM VERTICAL 2) NO DWV WATER TEST 3) NO POTABLE WATER TEST 4) NO GAS TEST 5) STOPPED INSPECTION |