Permit: T05CM05405

Inspection Status: Approved

Inspection History: BUILDING - FINAL

Permit Number - T05CM05405

Inspection Description - BUILDING - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
07/17/2006 BUILDING - FINAL Approved IVRS - Inspection :*
07/14/2006 BUILDING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) WHAT ARE NUTTED WIRES IN PANEL FOR ?
2) WHAT IS EXTRA 30 AMP BREAKER FOR ?
3) MARK A/C LABELS FOR UNIT ? TO CHECK DISCONNECT SIZE
4) INSTALL BONDING JUMPER ACCROSS NON-METALIC A/C BELLOWS
5) MUST REVISE PLAN TO SHOW NEW CLEANOUT LOCATION EAST OF GARAGE
6) GARAGE DOOR LOCKED
7) MARK PANEL NOT A WATER BONDED SYSTEM
8) CAULK BASE OF TOILETS
9) ASK SUPERINTENDENT TO SECURE OFF LADDER FOR ROOF ACCESS-HE SAID HE COULD NOT DO IT, WOULD RUIN ROOF. SUPER SAID TO DENY IT
10) STOPPED INSPECTION