Permit: T05CM05400

Inspection Status: Approved

Inspection History: EXT METAL CLIPS/EXT SHEATHING

Permit Number - T05CM05400

Inspection Description - EXT METAL CLIPS/EXT SHEATHING

Inspection Status - Approved

Date Description Inspector Results Comments
01/09/2006 EXT METAL CLIPS/EXT SHEATHING Approved IVRS - Inspection :*
01/06/2006 EXT METAL CLIPS/EXT SHEATHING Denied 1) SHEARWALLS MISSING MANY AREAS, H2.5, 135'S MISSING MANY AREAS
2) ANY DEVIATIONS FROM APPROVED PLAN TO BE APPROVED BY ENGINEER OF RECORD AND SUBMITTED TO CITY OF TUCSON PLAN CHECK FOR APPROVAL
3) STOPPED INSPECTION
01/05/2006 EXT METAL CLIPS/EXT SHEATHING Not ready for Inspection IVRS - Inspection :*
1) NO PLANS/PERMIT VISIBLE AT LOT LOCATION
01/03/2006 EXT METAL CLIPS/EXT SHEATHING Partial Approval IVRS - Inspection :*
1) COMPLETE ALL HOLDOWNS, SHEARWALLS ETC..., HAVE STANDARD REAR PORCH REMOVED FROM PLANS
2) WEST WALL EXTERIOR 5/8" X
3) FIRERATED ROCK AND INSIDE PARAPET OK
4) HAVE ALTERNATE FIREWALL ASBUILT APPROVED BY ENGINEER SUBMITTAL TO CITY OF TUCSON PLAN CHECK
12/23/2005 EXT METAL CLIPS/EXT SHEATHING Partial Approval IVRS - Inspection :*
1) INSPECTED FIREWALL ON WEST END OF HOME-APPROVED TO COVER
2) DBL BLOCKING AT ROOF DECK BETWEEN TRUSSES INSTALLED
3) APPROVED TO SHEATH
12/22/2005 EXT METAL CLIPS/EXT SHEATHING Not ready for Inspection IVRS - Inspection :*