Permit: T05CM05399

Parcel: 11304104E

Inspection Status: Approved

Inspection History: OUTDOOR LIGHTING FINAL

Date Description Inspector Results Comments
09/05/2006 OUTDOOR LIGHTING FINAL Approved IVRS - Inspection :*
08/28/2006 OUTDOOR LIGHTING FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
NOTE:
OVEN BREAKER TURNS OFF LIGHTING CKTS?
PROVIDE WATER HEATER DISCONNECT -- NEC 422.30
MARK PANEL DIRECTORIES PROPERLY -- NEC 408.4
PLUG CHECK ALL RECEPTS/GFI'S
INSTALL ANTI TIP FOR RANGE'S -- NEC 110.3
ARC FAULT PROTECTION FOR ALL BEDROOM RECEPTS, SMOKES, LIGHTS -- NEC 210.12
WHERE IS MICRO CKT?
GO THROUGH BOTH UNITS BEFORE CALLING FOR FINAL