Inspection History Details
Inspection Status: Approved
Inspection History: OUTDOOR LIGHTING FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/05/2006 | OUTDOOR LIGHTING FINAL | Approved | IVRS - Inspection :* | |
| 08/28/2006 | OUTDOOR LIGHTING FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* NOTE: OVEN BREAKER TURNS OFF LIGHTING CKTS? PROVIDE WATER HEATER DISCONNECT -- NEC 422.30 MARK PANEL DIRECTORIES PROPERLY -- NEC 408.4 PLUG CHECK ALL RECEPTS/GFI'S INSTALL ANTI TIP FOR RANGE'S -- NEC 110.3 ARC FAULT PROTECTION FOR ALL BEDROOM RECEPTS, SMOKES, LIGHTS -- NEC 210.12 WHERE IS MICRO CKT? GO THROUGH BOTH UNITS BEFORE CALLING FOR FINAL |