Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/10/2006 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 09/19/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : There is no access to the site.| 920* 1. GATE IS LOCKED 2. REMOVE AND DISCONNECT TEMPORARY SERVICE BEFORE FINAL APPROVAL |
|
| 09/07/2006 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* OK TO OCCUPY UNITS #1 & 2 FINISH GATE WIRING & SITE WIRING FOR LIGHTING |
|
| 09/05/2006 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* #1 1. WEST UNIT 5 RECEPTACLE BY AC UNIT TO BE GFI 2. RECEPTACLES AT END PENINSULA TO BE GFI, ALSO ISLAND #2 PENINSULA NOT ON GFI |
|
| 08/28/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* |