Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/10/2006 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 05/05/2006 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* | |
| 04/04/2006 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK CORRECTIONS, OK TO LOWER ELECTRICAL |
|
| 03/29/2006 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. STILL NEED FRONT AND REAR EXTERIOR OUTLET 2. STILL NEED TO IDENTIFY WHITE CONDUCTORS USES AS HOTS OK TO COVER ELECTRICAL AFTER CORRECTIONS. |
|
| 03/28/2006 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. HAVE BOXES OVERFILLED NEC 314.16 2. NEED NAIL PLATES IN SOME AREAS NEC 300.4 3. NEED LIGHT IN STAIRWAY NEC 210.70 (2) 4. IDENTIFY WHITE CONDUCTORS USED AS HOT NEC 200 5. NEED EXTERIOR OUTLET @ FRONT AND REAR OF EACH UNIT NEC 210.52 (E) 6. USE PROPER CRIMP TOOL FOR CRIMP SLEEVES NEC 110.3 (B) |