Permit: T05CM05399

Parcel: 11304104E

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
10/10/2006 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
05/05/2006 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
04/04/2006 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK CORRECTIONS, OK TO LOWER ELECTRICAL
03/29/2006 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. STILL NEED FRONT AND REAR EXTERIOR OUTLET
2. STILL NEED TO IDENTIFY WHITE CONDUCTORS USES AS HOTS
OK TO COVER ELECTRICAL AFTER CORRECTIONS.
03/28/2006 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. HAVE BOXES OVERFILLED NEC 314.16
2. NEED NAIL PLATES IN SOME AREAS NEC 300.4
3. NEED LIGHT IN STAIRWAY NEC 210.70 (2)
4. IDENTIFY WHITE CONDUCTORS USED AS HOT NEC 200
5. NEED EXTERIOR OUTLET @ FRONT AND REAR OF EACH UNIT NEC 210.52 (E)
6. USE PROPER CRIMP TOOL FOR CRIMP SLEEVES NEC 110.3 (B)