Permit: T05CM05399

Parcel: 11304104E

Inspection Status: Approved

Inspection History: EXCAVATION/LAYOUT REBAR & ZON

Date Description Inspector Results Comments
01/03/2006 EXCAVATION/LAYOUT REBAR & ZON Approved IVRS - Inspection :*
11/28/2005 EXCAVATION/LAYOUT REBAR & ZON Not ready for Inspection IVRS - Inspection :*SET BACKS DO NOT MATCH PLANS. CORRECT AND RECALL.
11/23/2005 EXCAVATION/LAYOUT REBAR & ZON Denied IVRS - Inspection :
See detailed listing on site.| 999*PLEASE REFER TO YOUR DETAILS FOR FOOTINGS
1) CODE REQUIRES BOTTOM OF FOOTING TO BE 12" MINIMUM INTO UNDISTURBED EARTH
YOUR DETAILS 101 AND 102 SHOW MINIMUM PER CODE. YOUR DETAIL 104 ASKS FOR 22" MIN DEPTH FOR SHEAR WALLS. PLEASE GET NOTE FROM ENGINEER DELETING DETAIL 104.
11/21/2005 EXCAVATION/LAYOUT REBAR & ZON Denied IVRS - Inspection :
See detailed listing on site.| 999*NO REBAR INFTG
NEED SPECIAL INSP. REPORT
MONO POOR REQUIRE PRE-SLAB/
POST TENSION NEEDS TO BE INDICATED ON PLANS.