Permit: T05CM05398

Parcel: 119421490

Inspection Status: Approved

Inspection History: FRAMING

Date Description Inspector Results Comments
02/17/2006 FRAMING Approved IVRS - Inspection :*
02/13/2006 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) LATH SEAL WEST WALL PENETRATIONS
2) 2" DIRTY ARM NOT ALLOWED AT LAV
3) WATER LINES NOT COMPLETE, RETEST DWV'S
4) SHEAR RAKE WALLS
5) SEE LAST INSPECTION
02/09/2006 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) REPLACE OVER NOTCHED STUDS AT GARAGE WALL
2) BLOCK OUT SHEAR AT GARAGE
3) DIRTY ARM IN HALL BATH CANNOT EXCEED 42" AND FIRE BLOCKS NOT TIGHT TO DROPPED CEILING
4) SHEAR TRANSFER WALL AT KITCHEN MISSING DBL TOP PLATE
5) PROVIDE BACKING BEHIND MASTER TUB
6) SEAL ALL PENETRATIONS FROM OUTSIDE AND INSIDE BARRIER
7) NAIL PROTECT VTR AT MASTER TOILET AREA AND WATER LINES AT TUB
8) SHIM HEADERS WHERE NEEDED
9) STOPPED INSPECTION-TO MANY ITEMS
02/07/2006 FRAMING Cancelled CANCELLED PER TITO OF STANDARD PACIFIC HOMES #240-9880