Permit: T05CM05384

Parcel: 11808060B

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
10/31/2005 PLUMBING - FINAL Approved IVRS - Inspection :*
10/28/2005 PLUMBING - FINAL Partial Approval IVRS - Inspection :*CONDENSATE DRAIN-IMPROPER TERMINATION.
CONTINUE TO GROUND WITH PROPER TERMINATION
PAINT PVC EXPOSED TO SUN.
ELECTRICAL
ELIMINATE EVAP ?? MIDWEST ??? CLEAR ACCESS PANEL TO UNIT FOR SERVICE
DROP GAS LINE AT UNIT TO CLEAR ACCESS PANELS. BLOCK & CLAMP AT UNIT GAS VALVE AS NECESSARY.
NEED B 1 VENT PIPE AND CAP, WATER HTR. UP TO TERMINATION. CUT PROPER CLEARANCE AT ROF SHEETING. SINGLE WALL CONNECTOR PIPE IS INCORRECT.
GAS PRESS TEST AT METER 16 PSI
NO ACCESS TO HOUSE TO CHECK ADDITIONAL APPLI.