Permit: T05CM05372

Parcel: 12709012C


Addresses:

6245 E BROADWAY BL

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
01/31/2006 ELECTRIC - FINAL Approved IVRS - Inspection :*
1) OK FINAL
01/26/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*CORRECTLY IDENTIFY CONDUCTORS 480 V SIDE
CONDUCTORS TO ENTER SECTION OF MOTOR CONTROL THAT SERVES CONDUCTORS 408.3
GROUNDING ELECTRODE TO BE INSTALLED PER 250.30
LABELING REQUIRED AS PER 702.8
TIGHTEN DAMDGED LUGS
TIGHTEN FITTINGS TO TUSS
TUSS NOT AS PER PLANS
CLEAN SURFACE UNDER LUG
SEPARATE GROUNDING AND GROUNDED CONDUCTORS-ALSO REMOVE BOND SCREW IF GROUNDED BUSS AT PANEL IN UNIT.