Permit: T05CM05369

Parcel: 10612017R

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
11/23/2005 ELECTRIC - FINAL Approved IVRS - Inspection :*OK ELECTRICAL FINAL. OK TEP CLEARANCE/RECON
11/21/2005 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*NEED LOCKNUTS AND BUSHINGS ON UNDERGROUND CONDUIT ( BOTH ENDS)
INSTALLL BONDING JUMPER IN SERVICE DISCONNECT
REMOVE BONDING JUMPER IN SUB PANLE
NORTH A.C UNIT DISCONNECT NEED K.O PLUG AND GFI NOT WIRED.
11/18/2005 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*NOT READY
11/17/2005 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*OUTSIDE CONDUIT FROM SERVICE TO PANEL REQUIRED TO BE 18" DEEP TO TOP OF PIPE NEC 2002 300-5 ITEMS 2 & 3 ALSO TO BE DONE
11/15/2005 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*CLASS R FUSES REQUIRE REJECT PINS
GROUND CUT TO MAIN SERVICE
UNDERGROUND FROM DISCONNECT TO NEW PNL NOT INSPECTED
SCRAPE PAINT BEHIND GROUND LUG IN MAIN DISCONNECT
SUB PANEL TO HAVE SCHEDULE
LP TO PANEL MISSING & SEAL OUTSIDE OPENING
INSTALL DEAD FRONT COVER-FILL CONDUCTORS INTO PANEL SO THEY DONT POP OUT
MEYERS HUB AT SUB PNL-2 SCREWS MISSING, 2 WRONG TYPE CLOSE ALL J-BOXES IN CEILING
FIXTURES IN CEILING TOHAVE SIEMIC TIES & SCREWS
EM LIGHTS & EXITS MISSING FA???
CEILING BOXES TO HAVE CIRCUITS ON THEM
ALL PLATES TO BE INSTALLED
ROOF ACCESS.
PLEASE REVIEW JOB FOR FINISHED STATE PRIOR TO RECALL