Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/23/2005 | ELECTRIC - FINAL | Approved | IVRS - Inspection :*OK ELECTRICAL FINAL. OK TEP CLEARANCE/RECON | |
| 11/21/2005 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245*NEED LOCKNUTS AND BUSHINGS ON UNDERGROUND CONDUIT ( BOTH ENDS) INSTALLL BONDING JUMPER IN SERVICE DISCONNECT REMOVE BONDING JUMPER IN SUB PANLE NORTH A.C UNIT DISCONNECT NEED K.O PLUG AND GFI NOT WIRED. |
|
| 11/18/2005 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999*NOT READY |
|
| 11/17/2005 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999*OUTSIDE CONDUIT FROM SERVICE TO PANEL REQUIRED TO BE 18" DEEP TO TOP OF PIPE NEC 2002 300-5 ITEMS 2 & 3 ALSO TO BE DONE |
|
| 11/15/2005 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999*CLASS R FUSES REQUIRE REJECT PINS GROUND CUT TO MAIN SERVICE UNDERGROUND FROM DISCONNECT TO NEW PNL NOT INSPECTED SCRAPE PAINT BEHIND GROUND LUG IN MAIN DISCONNECT SUB PANEL TO HAVE SCHEDULE LP TO PANEL MISSING & SEAL OUTSIDE OPENING INSTALL DEAD FRONT COVER-FILL CONDUCTORS INTO PANEL SO THEY DONT POP OUT MEYERS HUB AT SUB PNL-2 SCREWS MISSING, 2 WRONG TYPE CLOSE ALL J-BOXES IN CEILING FIXTURES IN CEILING TOHAVE SIEMIC TIES & SCREWS EM LIGHTS & EXITS MISSING FA??? CEILING BOXES TO HAVE CIRCUITS ON THEM ALL PLATES TO BE INSTALLED ROOF ACCESS. PLEASE REVIEW JOB FOR FINISHED STATE PRIOR TO RECALL |