Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - ABOVE CEILING
Permit Number - T05CM05367
Inspection Description - MECHANICAL - ABOVE CEILING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/16/2006 | MECHANICAL - ABOVE CEILING | Approved | PER INSP CARD | |
02/13/2006 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* NEED SMOKE ALARMS! |
|
02/03/2006 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) AREA IN REAR OF STORE IS NOT CONDITIONED SPACE 2) PROVIDE MINIMUM R5 INSULATION 3) PROVIDE FRESH AIR INTAKES, DUCT SMOKE DETECTORS, CONDENSATE DRAINS, CHILLER AND BOILER PIPING |