Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/06/2006 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection :* | |
| 01/04/2006 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) AGE AND DUE TO VANDALISM AND DILAPIDATION OF THE EXISTING SERVICE AND ELECTRICAL SYSTEM THE FOLLOWING NEEDS TO BE REPAIRED OR BROUGHT UP TO A SAFE CONDITION 2) REPLACE PANEL M FEEDER THEY ARE PRESENTLY IN HAZZARDOUS CONDITIONS AND SHORT 3) INSTALL PROTECTIVE BUSHINGS ON ALL CONDUITS WITH #4 OR LARGER CONDUCTORS 4) INSTALL EQUIPMENT GROUNDING CONDUCTORS AS REQUIRED PER NEC THROUGHOUT 5) INSTALL EQUIPMENT GROUNDING BUS BARS AT ALL SUB PANELS 6) INSTALL BOND BUSHINGS ON EQUIPMENT AS DISCUSSED WITH ELECTRICAL CONTRACTOR 7) INSTALL GROUNDING ELECTRODE SYSTEM AND CONDUCTOR PER NEC ART 250 |