Permit: T05CM05361

Parcel: 116213020


Addresses:

839 W CONGRESS ST


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T05CM05361

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
06/26/2006 ELECTRIC - FINAL Approved 1) NOTE: TRIM RECEPTACLES IN EAST WALL IN MED ROOM AND BOND TRANSFORMER GROUNDING ELECTRODE CONDUCTOR DIRECTLY TO BLDG STEEL
06/23/2006 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
06/21/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
COMPLETE ALL CORRECTIONS BEFORE INSPECTION.
04/28/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
OK TO OCCUPY FOR THE PURPOSE OF SETTING UP OFFICES.
1. HEATER/RTU CKT IS UNDERSIZED NEC 220
2. NEED BUSHING #4 AND LARGER WIRE - NEC 300
3. NEED K.O PLUG ON GEAR.
4. VERIFY THAT BUILDING STEEL IS GROUNDED NEC 250.30 (4)
5. RACEWAY FOR G.E.C NEEDS TO BE ELECTRICALLY CONTINUOUS - NEC 250.64
6. USE PROPER LUG/CONNECTIONS FOR GROUNDS IN TRANSFORMER - NEC 110
04/28/2006 ELECTRIC - FINAL Partial Approval OK FOR TEMP C OF O FOR SETTING UP OFFICES
04/26/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*