Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T05CM05361
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/26/2006 | ELECTRIC - INTERMEDIATE | Approved | ||
| 06/21/2006 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* |
|
| 06/19/2006 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. COVER ALL OPENINGS IN J-BOXES 2. IDENTIFY ALL BOXES RED THAT HAVE FIRE ALARM TERMINATIONS. 3. SUPPORT CONDUIT AS NEEDED 4. REMOVE OR TAG ALL ABANDONED LOW VOLTAGE WIRING. |
|
| 06/08/2006 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK ELECTRICAL WALL COVER PHARMACY AREA AFTER CORRECTIONS. 1. INSTALL K.O BLANKS AS NEEDED. 2. INSTALL PROPER SIZE MUD RINGS. 3. STRAP EMT AS NEEDED. |
|
| 06/01/2006 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK TO COVER ELECTRICAL FOR NEW LIGHTING IN RECEPTION LOBBY CEILING - STILL NEED TO SEE LIGHTING ENERGIZED. |
|
| 05/24/2006 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK TO COVER ELECTRICAL IN STAFF AREA SOUTH AND WEST WALLS. *NOTE* EXISTING OUTLET ON SOUTH WALL NOT THERE PER PLAN? |
|
| 05/18/2006 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK ELECTRICAL COVER IN WALLS/HARD LIDS IN CONSULTATION AREA. |
|
| 05/16/2006 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. FINISH DEMOLITION OF WIRING AND RACEWAYS. 2. REMOVE, TAG, LOW VOLTAGE WIRING AND RUN LOW VOLTAGE WIRING IN A WORKMAN (NEAT) LIKE MANNER. 3. INSTALL KO BLANKS AND STRAP RACEWAYS AS NEEDED. 4. INSTALL PROPER SIZE MUD RINGS AS NEEDED. |
|
| 04/28/2006 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* |
|
| 04/27/2006 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. SEPARATELY DERIVED SYSTEM NEEDS TO BE GROUNDED PER NEC 250.30 (TRANSFORMER). 2. PROVIDE PROPER CLEARANCE TO COMBUSTIBLES AND SECURE TRANSFORMER TO FLOOR. 3. TIGHTEN ALL SCREWS FOR GROUNDING/BONDING CONDUCTORS NEC 110/250 4. FINISH WIRING TO RTU & SECURE DISCONNECT. 5. SECURE FEEDER RACEWAY TO STRUCTURE (ROOF) NEC 358 6. P.I FEEDERS NOT ALLOWED TO CROSS SECTIONS IN SWITCHGEAR NEC 408.3(3) |
|
| 04/26/2006 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. NEED PANELS AND TRANSFORMER OPEN FOR INSPECTION. 2. PANEL DIRECTORY NOT MARKED 3. LOW VOLTAGE WIRING IN CEILING NOT SUPPORTED 4. CHECK EMERGENCY LIGHTING THAT IT IS PER PLAN. 5. FIXTURES NEED TO BE SECURED TO GRID. 6. EXIT NEEDS SLACK WIRES. 7. CHECK BOX FILL IN CEILING. INSPECTION TO CONTINUE AFTER EQUIPMENT OPEN. |
|
| 03/14/2006 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK TO COVER ELECTRICAL IN WALLS AND HARD LIDS - PHASE 1 *NOTE - MAKE SURE DEMO OF OLD/ABANDONED WIRING IS COMPLETE AND SAFED OFF |