Permit: T05CM05361

Parcel: 116213020


Addresses:

839 W CONGRESS ST


Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Permit Number - T05CM05361

Inspection Description - ELECTRIC - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
06/26/2006 ELECTRIC - INTERMEDIATE Approved
06/21/2006 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
06/19/2006 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. COVER ALL OPENINGS IN J-BOXES
2. IDENTIFY ALL BOXES RED THAT HAVE FIRE ALARM TERMINATIONS.
3. SUPPORT CONDUIT AS NEEDED
4. REMOVE OR TAG ALL ABANDONED LOW VOLTAGE WIRING.
06/08/2006 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK ELECTRICAL WALL COVER PHARMACY AREA AFTER CORRECTIONS.
1. INSTALL K.O BLANKS AS NEEDED.
2. INSTALL PROPER SIZE MUD RINGS.
3. STRAP EMT AS NEEDED.
06/01/2006 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK TO COVER ELECTRICAL FOR NEW LIGHTING IN RECEPTION LOBBY CEILING - STILL NEED TO SEE LIGHTING ENERGIZED.
05/24/2006 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK TO COVER ELECTRICAL IN STAFF AREA SOUTH AND WEST WALLS.
*NOTE* EXISTING OUTLET ON SOUTH WALL NOT THERE PER PLAN?
05/18/2006 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK ELECTRICAL COVER IN WALLS/HARD LIDS IN CONSULTATION AREA.
05/16/2006 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. FINISH DEMOLITION OF WIRING AND RACEWAYS.
2. REMOVE, TAG, LOW VOLTAGE WIRING AND RUN LOW VOLTAGE WIRING IN A WORKMAN (NEAT) LIKE MANNER.
3. INSTALL KO BLANKS AND STRAP RACEWAYS AS NEEDED.
4. INSTALL PROPER SIZE MUD RINGS AS NEEDED.
04/28/2006 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
04/27/2006 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. SEPARATELY DERIVED SYSTEM NEEDS TO BE GROUNDED PER NEC 250.30 (TRANSFORMER).
2. PROVIDE PROPER CLEARANCE TO COMBUSTIBLES AND SECURE TRANSFORMER TO FLOOR.
3. TIGHTEN ALL SCREWS FOR GROUNDING/BONDING CONDUCTORS NEC 110/250
4. FINISH WIRING TO RTU & SECURE DISCONNECT.
5. SECURE FEEDER RACEWAY TO STRUCTURE (ROOF) NEC 358
6. P.I FEEDERS NOT ALLOWED TO CROSS SECTIONS IN SWITCHGEAR NEC 408.3(3)
04/26/2006 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. NEED PANELS AND TRANSFORMER OPEN FOR INSPECTION.
2. PANEL DIRECTORY NOT MARKED
3. LOW VOLTAGE WIRING IN CEILING NOT SUPPORTED
4. CHECK EMERGENCY LIGHTING THAT IT IS PER PLAN.
5. FIXTURES NEED TO BE SECURED TO GRID.
6. EXIT NEEDS SLACK WIRES.
7. CHECK BOX FILL IN CEILING.
INSPECTION TO CONTINUE AFTER EQUIPMENT OPEN.
03/14/2006 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK TO COVER ELECTRICAL IN WALLS AND HARD LIDS - PHASE 1
*NOTE - MAKE SURE DEMO OF OLD/ABANDONED WIRING IS COMPLETE AND SAFED OFF