Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
Permit Number - T05CM05343
Inspection Description - PLUMBING - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/17/2006 | PLUMBING - INTERMEDIATE | Approved | IVRS - Inspection :* ALL CORRECTIONS OK EXCEPT THAT #4 DID NOT GET CHANGED. |
|
05/12/2006 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* | |
05/12/2006 | PLUMBING - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. NO CONCEALED PLASTIC THREADS. USE WYE W/PERM CAP OR CLEAN OUT FITTING W/ACCESSIBLE THREADS FOR TEST. 2. VENT FOR SINK IN SPACE NEXT DOOR HAS BEEN CUT NEAR FIXTURE D-11 IN RM 112. DO NOT COVER. CORRECT VENT. D-9 FIXTURES CALL FOR ISLAND VENTING. PROVIDE REVISION OR INSTALL PER PLAN. 3. TRAP PRIMER NOT INSTALLED. REQUIRES A.P 4. DRAWING SHOWS CLEAN OUT FOR P-7 OPENING INTO ROOM W/FIXTURE. 5. OVER HEAD COPPER TO BE SUPPORT AT 6' INTERVALS 6. OVER HEAD COPPER IS NOT INSULATED. 7. CLOSET FLANGES NOT PROPERLY INSTALLED. |