Inspection Status: Approved

Inspection History: PLUMBING - INTERMEDIATE

Permit Number - T05CM05343

Inspection Description - PLUMBING - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
05/17/2006 PLUMBING - INTERMEDIATE Approved IVRS - Inspection :*
ALL CORRECTIONS OK EXCEPT
THAT #4 DID NOT GET CHANGED.
05/12/2006 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
05/12/2006 PLUMBING - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. NO CONCEALED PLASTIC THREADS. USE WYE W/PERM CAP OR CLEAN OUT FITTING W/ACCESSIBLE THREADS FOR TEST. 2. VENT FOR SINK IN SPACE NEXT DOOR HAS BEEN CUT NEAR FIXTURE D-11 IN RM 112. DO NOT COVER. CORRECT VENT. D-9 FIXTURES CALL FOR ISLAND VENTING. PROVIDE REVISION OR INSTALL PER PLAN.
3. TRAP PRIMER NOT INSTALLED. REQUIRES A.P
4. DRAWING SHOWS CLEAN OUT FOR P-7 OPENING INTO ROOM W/FIXTURE.
5. OVER HEAD COPPER TO BE SUPPORT AT 6' INTERVALS
6. OVER HEAD COPPER IS NOT INSULATED.
7. CLOSET FLANGES NOT PROPERLY INSTALLED.