Permit: T05CM05339
Inspection Status: Approved
Inspection History: FRAMING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/23/2006 | FRAMING | Approved | IVRS - Inspection :* | |
| 03/22/2006 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) WATER HEATER B-VENT OFF SET CANNOT EXCEED 60 DEGREE FROM VERTICAL 2) GROUND METAL ELECTRIC BOX HALL BATH 3) FURNACE B-VENT OFF SET CANNOT EXCEED 10 DEGREE FROM VERTICAL 4) FIRE STOP CHASES IN BEDROOMS 5) STAIRS NOT SUPPORTED PER 49/AD3 6) NAIL PROTECT PLUMBING |
|
| 03/20/2006 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. POTABLE HW TEST HOLDING 2. DWV TEST HOLDING 3. GAS TEST HOLDING 4. NEED TO NAIL PROTECT PLB 5. ITEM #6 NOT ADDRESSED? STOPPED INSPECTION |
|
| 03/10/2006 | FRAMING | Denied | IVRS - Inspection : Work is not complete enough to inspect.| 950* 1) NAIL PROTECT PLUMBING 2) PLUMBING OUT OF WALL 3) NO DWV TEST 4) NO GAS TEST 5) NO POTABLE WATER TEST 6) B-VENT LAV NOT TO EXCEED 60" FROM ? 7) STOPPED INSPECTION |