Permit: T05CM05326

Parcel: 125076370

Inspection Status: Approved

Inspection History: PLUMBING - INTERMEDIATE

Permit Number - T05CM05326

Inspection Description - PLUMBING - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
02/21/2006 PLUMBING - INTERMEDIATE Approved IVRS - Inspection :*MET WITH G.C AND PLUMBING CONTRACTOR WE RESOLVED ALL ISSUES
OK TO COER ALL AREAS
02/07/2006 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
12/21/2005 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
1) REMOVE ALL ROCK AND DEBIS FROM TRENCH
2) A DRAIN MAY NOT DUMP INTO A VENT
3) WET VENTING IS LIMITED TO VERTICAL DRAINAGE PIPING
4) RED LINE NOT APPROVED
12/21/2005 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. CORRECTION MADE OK - CONTRACTOR TO REMOVE ROCKS AND DEBRIS FROM TRENCH AS PREVIOUSLY REQUESTED.
2. OK TO COVER UNDERGROUND
11/30/2005 PLUMBING - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*NO THREADED ABS PLASTIC FITTING SHALL BE IN AN UNEXPOSED LOCATION.
SHALLPROVIDE LONG RADIUS DRAINAGE FITTINGS
SHALL PROVIDE MINIMUM 1/4" PER ROOT FALL ON ALL DRAINAGE PIPING.
PROVIDE RED LINE OF YOUR INSTALLATION.
PROVIDE PIPE WRAP AT PENETRATION THRU CONCRETE.
MAKE CONNECTION TO BUILDING DRAIN & PROVIDE CORRECT TEST METHOD.
11/18/2005 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*