Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
Permit Number - T05CM05326
Inspection Description - PLUMBING - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/21/2006 | PLUMBING - INTERMEDIATE | Approved | IVRS - Inspection :*MET WITH G.C AND PLUMBING CONTRACTOR WE RESOLVED ALL ISSUES OK TO COER ALL AREAS |
|
02/07/2006 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* | |
12/21/2005 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* 1) REMOVE ALL ROCK AND DEBIS FROM TRENCH 2) A DRAIN MAY NOT DUMP INTO A VENT 3) WET VENTING IS LIMITED TO VERTICAL DRAINAGE PIPING 4) RED LINE NOT APPROVED |
|
12/21/2005 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. CORRECTION MADE OK - CONTRACTOR TO REMOVE ROCKS AND DEBRIS FROM TRENCH AS PREVIOUSLY REQUESTED. 2. OK TO COVER UNDERGROUND |
|
11/30/2005 | PLUMBING - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999*NO THREADED ABS PLASTIC FITTING SHALL BE IN AN UNEXPOSED LOCATION. SHALLPROVIDE LONG RADIUS DRAINAGE FITTINGS SHALL PROVIDE MINIMUM 1/4" PER ROOT FALL ON ALL DRAINAGE PIPING. PROVIDE RED LINE OF YOUR INSTALLATION. PROVIDE PIPE WRAP AT PENETRATION THRU CONCRETE. MAKE CONNECTION TO BUILDING DRAIN & PROVIDE CORRECT TEST METHOD. |
|
11/18/2005 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* |