Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/06/2006 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* 1) OK FINAL |
|
| 02/17/2006 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. BOXES MORE THAN 1/4" FROM BOX TO SURFACE NEED AN APPROVED EXTENDER RNG 314.20 2. 4 DISCONNECTING MEANS IS NEEDED FOR INSTA HOT 3. REVISE PLANS FOR AC'S |
|
| 02/15/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* THE PLANS DO NOT SHOW FAN COILS 1 & 2 CV #1 ON ROOF -- CV #2 ON ROOF DID NOT INSPECT THESE ON INTERMEDIATE OR CEILING INSPECTIONS THEY WERE NOT ON PLANS AND HAVE BEEN ADDED AFTER |