Permit: T05CM05326

Parcel: 125076370

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Permit Number - T05CM05326

Inspection Description - ELECTRIC - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
12/20/2005 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*APPROVED
12/02/2005 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999$ MESSAGE DID NOT GO THRU
TRIED RETREIVING MESSAGE FROM SYSTEM, THERE WASN'T ONE THERE.
11/30/2005 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :* # 1 WATER HEATER ON PANEL SCHEDULE SHOWS 35 AMP BREAKER- # 12 WIRE TOO SMALL
#2 PLAN SHOWS 3 COLUMNS ON N & S WALLS ONLY 2 PUT IN-ARE OTHERS OMITTED?
11/17/2005 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*RECEPTACLES IN PANEL ROOM MISSING
WH POWER SUPPLY NOT IN EX ?? NOT IN ( CAN BE DONE IN CEILING INSP)