Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - YARD WTR LINE/TEST
Permit Number - T05CM05324
Inspection Description - PLUMBING - YARD WTR LINE/TEST
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/26/2006 | PLUMBING - YARD WTR LINE/TEST | Approved | IVRS - Inspection :* | |
09/18/2006 | PLUMBING - YARD WTR LINE/TEST | Denied | IVRS - Inspection : See detailed listing on site.| 999* PROVIDE 12" OF COVER OVER PVC USE PVC THAT IS NOT SUN DAMAGED LOCATE AND SECURE TRACER WIRE. |
|
08/30/2006 | PLUMBING - YARD WTR LINE/TEST | Partial Approval | IVRS - Inspection :* 60 PSI TEST FROM METER LOCATION PVC SCH 40 TO 5' FROM EXISTING BUILDING STUDS OK SHALL SEE METER THRU RPB CONNECTIONS + CONNECTION TO BUILDING. |
|
08/25/2006 | PLUMBING - YARD WTR LINE/TEST | Not ready for Inspection | IVRS - Inspection :* | |
07/12/2006 | PLUMBING - YARD WTR LINE/TEST | Partial Approval | IVRS - Inspection :* 2" STUBBED UP & OUT 5' SOUTHEAST CORNER 60+ TEST OK |