Inspection Status: Approved
Inspection History: ELECTRIC - UNDERGROUND
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/27/2007 | ELECTRIC - UNDERGROUND | Approved | IVRS - Inspection :* | |
| 11/17/2006 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* OK SERVICE UNDERGROUND MAKE SURE WARNING RIBBON INSTALLED - NEC 300.5 D3 |
|
| 11/16/2006 | ELECTRIC - UNDERGROUND | Denied | IVRS - Inspection : See detailed listing on site.| 999* INSPECTION FOR SERVICE RACEWAY ONLY 1. WHERE IS GROUNDING ELECTRODE FOR SERVICE? 2. SERVICE RACEWAY NEEDS WARNING RIBBON MINIMUM 12" ABOVE RACEWAYS NEC 230 |