Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/07/2006 | PLUMBING - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 03/31/2006 | PLUMBING - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* READ NOTES FROM PAST INSPECTINOS AND PROVIDE CONNECTIONS. |
|
| 03/29/2006 | PLUMBING - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. PROVIDE LONG RADIUS DRAINAGE FITTINGS FOR HORIZONTAL CHANGE OF DIRECTION AT LAVS. 2. PROVIDE CORRECT SUPPORT & SECURE HORIZONTAL VENT PIPING OVERHEAD. 3. PROVIDE MINIMUM 18" COPPER IN WALL FOR WATER HEATER PER MANUFACTURERS DIRECTION. |