Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
Permit Number - T05CM05289
Inspection Description - FRAMING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/09/2006 | FRAMING | Approved | IVRS - Inspection :* | |
03/02/2006 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) THE FORCED AIR UNITS USED ON THIS SITE ARE NOT AS LISTED ON THE PLAN. THE NEW UNITS REQUIRED 35 AMP DRAIN. THE PRESENT PLANS SHO 10 GAUGE WIRE. HAVE YOUR PLANS REVISED FOR CORRECT F.A.U. AND WIRE 2) INCORRECT HOLDOWNS INSTALLED MTS-27B REQUIRED 3) TRUSS REPAIR NOT MADE 4) TRUSS SHEAR PANELS REQUIRED EACH BAY 4/SD2 5) UFERS CUT-INSTALL GROUND ROD 6) NO DWV WATER TEST 7) STOPPED INSPECTION-TOO MANY ITEMS |
|
02/27/2006 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) COMPLETE LATH AT GABLES 2) NAIL/STAPLE LATH 6" ON CENTER AT TOP OF PATIO 3) TIGHTEN AB'S 4) BANG PLATES ON ELECTRIC THROUGHOUT 5) STAPLES BEHIND HOME RUNS 6) WIRE SHEATHING MUST EXTEND INTO BOX-L.R. 7) BLOWN FIRE BLOCK AT ENTRY 8) SEAL VAPOR BARRIER 9) DAMAGED TRUSS END AT L.R. 10) STOPPED INSPECTION-HOUSE NOT READY |