Permit: T05CM05289

Parcel: 141092330


Addresses:

7856 S SPLINTER WY


Inspection Status: Approved

Inspection History: FRAMING

Permit Number - T05CM05289

Inspection Description - FRAMING

Inspection Status - Approved

Date Description Inspector Results Comments
03/09/2006 FRAMING Approved IVRS - Inspection :*
03/02/2006 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) THE FORCED AIR UNITS USED ON THIS SITE ARE NOT AS LISTED ON THE PLAN. THE NEW UNITS REQUIRED 35 AMP DRAIN. THE PRESENT PLANS SHO 10 GAUGE WIRE. HAVE YOUR PLANS REVISED FOR CORRECT F.A.U. AND WIRE
2) INCORRECT HOLDOWNS INSTALLED MTS-27B REQUIRED
3) TRUSS REPAIR NOT MADE
4) TRUSS SHEAR PANELS REQUIRED EACH BAY 4/SD2
5) UFERS CUT-INSTALL GROUND ROD
6) NO DWV WATER TEST
7) STOPPED INSPECTION-TOO MANY ITEMS
02/27/2006 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) COMPLETE LATH AT GABLES
2) NAIL/STAPLE LATH 6" ON CENTER AT TOP OF PATIO
3) TIGHTEN AB'S
4) BANG PLATES ON ELECTRIC THROUGHOUT
5) STAPLES BEHIND HOME RUNS
6) WIRE SHEATHING MUST EXTEND INTO BOX-L.R.
7) BLOWN FIRE BLOCK AT ENTRY
8) SEAL VAPOR BARRIER
9) DAMAGED TRUSS END AT L.R.
10) STOPPED INSPECTION-HOUSE NOT READY