Permit: T05CM05285

Parcel: 141092400


Addresses:

7845 S SPLINTER WY


Inspection Status: Approved

Inspection History: SHEET ROCK NAILING

Permit Number - T05CM05285

Inspection Description - SHEET ROCK NAILING

Inspection Status - Approved

Date Description Inspector Results Comments
05/16/2006 SHEET ROCK NAILING Approved
05/08/2006 SHEET ROCK NAILING Denied IVRS - Inspection :
There is no access to the site.| 920*
1) HOUSE LOCKED-NO ACCESS
05/01/2006 SHEET ROCK NAILING Denied IVRS - Inspection :
See detailed listing on site.| 999*
3/4 BOLTS EPOXYED IN
REPAIR DOCUMENTS NOT ON SITE.
LDD APPROVED BOLTS.
04/21/2006 SHEET ROCK NAILING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) DBL STUDS NOT NAILED THRU OSB PER REPAIR DOCUMENT
2) FINAL INSPECTION NOT READY UNTIL HOLDOWNS PASS. PROVIDE HOLDOWN REPAIR DOCUMENTS
03/21/2006 SHEET ROCK NAILING Partial Approval IVRS - Inspection :*
1) DRYWALL OK BUT SHEARWALL ANCHOR BOLTS WERE NOT WET SET PER PLAN. PROVIDE ENGINEERS APPROVEDF REPAIR
03/20/2006 SHEET ROCK NAILING Denied IVRS - Inspection :
The drywall is not nailed per code.| 175*
1. SHEAR WALLS NOT NAILED PER PLAN
2. GARAGE SHEAR WALL 3 HOLD DOWNS REQUIRE WET SET 3/4" ANCHOR BOLTS. RED HEADS INSTALLED - PROVIDE ENGINEERING REPAIR
03/17/2006 SHEET ROCK NAILING Denied IVRS - Inspection :
The drywall is not nailed per code.| 175*
1) SHEARWALLS ? REQUIRE TOP AND BOTTOM PLATES NAILED AT 7" ON CENTER-NO 8" ON CENTER