Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/16/2006 | FRAMING | Approved | ||
| 03/20/2006 | FRAMING | Partial Approval | ||
| 03/09/2006 | FRAMING | Approved | IVRS - Inspection :* | |
| 03/03/2006 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) CIRCUIT CONDUCTORS MIGHT CONTACT BUSS BAR. TAPE ALL UNUSED WIRE ENDS 2) NO ADDRESS IN PANEL 3) HEADER 2 X CANNOT BE IN FLAT 4) INTERIOR BEARING WALL MAXIMUM SPACING 24" ON CENTER EXCEEDED |
|
| 02/23/2006 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) BEARING POST CUT AT LIVING ROOM DUCT 2) OVER SPAN LIVING ROOM/BATH 3) ITEM 03050 NOT APPLICABLE PER PAPERWORK TURNED IN BY INSPECTOR |
|
| 02/22/2006 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) PROVIDE LATH BACKER FOR ? STUCCO TO AT PORCH 2) SHIM HEADERS THROUGHOUT 3) NAIL PROTECT WIRES WITHIN 1 1/4" OF STUD/PLATE SURFACES 4) NO DWV WATER TEST 5) FIRE BLOCK KITCHEN CHASE 6) SHIM HEADERS THROUGHT 7) INSTALL ANCHOR BOLTS WITHIN 12" OF SPLICES 8) PROVIDE HEADER AT CUT BEARING STUD BY LR DUCT 9) FIRE BLOCK LIVING ROOM AT TOILET |