Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
Permit Number - T05CM05284
Inspection Description - FRAMING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/28/2006 | FRAMING | Approved | IVRS - Inspection :* | |
04/12/2006 | FRAMING | Partial Approval | IVRS - Inspection :* 1) UNDERSIZED HEADER HALL NEED 3 1/2" X 4 3/8" 2) CONNECT EXHAUST FAN REAR BATCH, BANG PLATE ROMEX REAR WALL T/PLT |
|
04/07/2006 | FRAMING | Not ready for Inspection | IVRS - Inspection :* 1) NOT READY PER SUPER |
|
04/04/2006 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) NAIL DBL STUDS PER REPAIR DOCUMENT 2) FIRE BLOCK FRONT WINDOW 3) 6/SD3 NOT COMPLIED WITH (REPEAT) 4) ELECTRIC BOXES MOVED-MAKE REPAIRS |
|
03/30/2006 | FRAMING | Not ready for Inspection | IVRS - Inspection :* 1) SAME AS BEFORE NOT READY |
|
03/16/2006 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) PLAN CALLS FOR WET SET ANCHOR BOLTS FOR GARAGE HOLDOWNS. ? ANCHORS USED PROVIDE ENGINEERING AND CITY APPROVED REPAIR 2) WRONG GARAGE HOLDOWNS INSTALLED 3) 6/SD3 NOT COMPLIED WITH 4) 4/SD2 NOT COMPLIED WITH AT TOP PLATES 5) INTERIOR BEARING WALLS REQUIRED 1/2" ANCHOR BOLTS WITHIN 12" OF ENDS AND EVERY 6 LF OR PROVIDE ENGINEERING DETAIL 6) FIRE BLOCK MISSING AT ENTRY 7) WIRE MASTER BATH FAN 8) S.D. WIRE BELOW CEILING 2 BEDROOM |