Permit: T05CM05283

Parcel: 141092370


Addresses:

7832 S SPLINTER WY


Inspection Status: Approved

Inspection History: FRAMING

Permit Number - T05CM05283

Inspection Description - FRAMING

Inspection Status - Approved

Date Description Inspector Results Comments
05/03/2006 FRAMING Approved IVRS - Inspection :*
04/24/2006 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) STUCCO COVERED WITHOUT INSPECTION
2) STUCCO WEEP SCREED MUST EXTEND 2" BELOW BOTTOM OF SILL PLATE. PROVIDE STUCCO WEEP SCRRED ICBO REPORT AND INSTALLATION STANDARDS
3) WIRES TRAPPED BY ADDED STUD
4) OSB SHEAR CANNOT BREAK BETWEEN STUDS
5) PROVIDE ENGINEERING REPAIR DOCUMENTS FOR RETRO HOLDOWN BOLTS
6) SHEAR WALL ? MUST BE NAILED AT 3" ON CENTER ON ENDS AND EDGES
7) INTERMEDIATES NOT COMPLETE
03/03/2006 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) OK TO INSULATE AND DRYWALL ALL BUT BR 3 SHEARWALL
2) PROVIDE PROOF THAT MTS 27B HOLDOWNS HAVE 9" EMBEDIMENT. THEY APPEAR TO BE EXPANSION (RED HEAD) BOLTS AND SHOULD BE EPOXY SET
02/22/2006 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) OK TO INSULATE
2) ITEM 3 AND 4 OF 2/16/06 NOT DONE
3) GARAGE SHEAR WALL 2 REQUIRES ANCHOR BOLTS PER S-3
02/16/2006 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) NO DWV WATER TEST
2) NO POTABLE WATER PRESSURE TEST
3) INCORRECT HOLDOWNS ON GARAGE SHEARWALL SHOULD BE MTS 27B
4) ANCHOR BOLTS REQUIRED WITHIN 12" OF PLATE SPLICE
5) BEDROOM 2 SMOKE DETCTOR MUST BE 18" FROM CORNER-NOTE 16, G1
6) MAKE UP AIR NOT THRU ROOF