Permit: T05CM05282

Parcel: 141092360


Addresses:

7838 S SPLINTER WY


Inspection Status: Approved

Inspection History: EXT METAL CLIPS/EXT SHEATHING

Permit Number - T05CM05282

Inspection Description - EXT METAL CLIPS/EXT SHEATHING

Inspection Status - Approved

Date Description Inspector Results Comments
05/03/2006 EXT METAL CLIPS/EXT SHEATHING Approved IVRS - Inspection :*
03/27/2006 EXT METAL CLIPS/EXT SHEATHING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) NO REVISION AS REQUESTED ON PREVIOUS INSPECTION
03/15/2006 EXT METAL CLIPS/EXT SHEATHING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) HEADER POSTS ARE NOT BEARING DBL TOP PLATES
2) ANCHOR INTERIOR BEARING WALLS
3) ANCHOR POSTS BEARING HEADERS IN HALL
4) 14/DT1 MUST BEAR ON DBL TOP PLATES AND ROOF SHEATHING
5) REVISE PLAN FOR TWO INTER HEADER RELOCATIONS AND CHANGE TO INCLUDE TRUSS TO FLOOR CONNECTIONS
6) 14/DT1 NOT NAILED OR BUILT TO PLAN
7) ROOF INSPECTION NOT MADE
02/16/2006 EXT METAL CLIPS/EXT SHEATHING Denied IVRS - Inspection :
Work is not complete enough to inspect.| 950*
1) 14/DT1 SHEARPANELS MUST EXTEND FROM DBL TOP PLATE TO ROOF SHEATHING
2) TRUSSES ARE NOT PER APPROVED TRUSS DRAWINGS AND ARE NOT INSTALLED PER OTHER DRAWINGS
3) BUILD TO PLAN OR REVERSE PLAN TO AS BUILT
4) STOPPED INSPECTION