Inspection History Details
Permit: T05CM05272
Inspection Status: Approved
Inspection History: PLUMBING - YARD WTR LINE/TEST
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/28/2007 | PLUMBING - YARD WTR LINE/TEST | Approved | IVRS - Inspection :* BLDG. CONNECTION MADE OK OK TO COVER |
|
| 06/22/2007 | PLUMBING - YARD WTR LINE/TEST | Partial Approval | IVRS - Inspection :* 1" IRRIGATION RPPBP INSTALLED OK |
|
| 06/18/2007 | PLUMBING - YARD WTR LINE/TEST | Partial Approval | IVRS - Inspection :* NEED TO SEE CONNECTIONS AT BLDG OK TO COVER THE REST |
|
| 04/16/2007 | PLUMBING - YARD WTR LINE/TEST | Not ready for Inspection | IVRS - Inspection :* WHO INSTALLED 2" DOM. SW FROM METER THRU RPPBP CONNECTING 3" BUILDING SUPPLY DOWNSTREAM OF 2" RPPBP WILL CAUSE PRESSURE DROP; ACTIVATING THE DEVICE PROVIDE ENGINEERING FOR THIS METHOD SEE 610.2 94 UPC INLET AND OUTLET AND ALL CONNECTING PIPING TO BE THE SAME SIZE AS BUILDING SUPPLY (3") |